User manual - ECOM0010 61
14
WF
Cycle Time
Cycle time (for a switch PID control distance: 10/ 15, for
the PID on SSR: 1) or servo time (declared by the manufac-
turer of the servo-motor)
Word modbus 2014
LabSoftView:
TFDPOET
Default: 1
E.g. : 1 = 1 seconds
Modbus:
UFOUITPGTFDPOET
E.g. : 10 = 1.0 seconds
15
//RS
Lower Limit Output Percentage
Selects min. value for control output percentage.
Word modbus 2015
0..100 % > Default: 0%
16
X/RS
Upper Limit Output Percentage
Selects max. value for control output percentage.
Word modbus 2016
0..100 % > Default: 100%
17
GH*U
Degree
Selects degree type.
Word modbus 2017
0 Centigrades. > Default
1 Fahrenheit.