Celduc Temperature controller ECOM Manuale Utente Pagina 61

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 103
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 60
62 ECOM0010 - User manual
18
D/
Alarm 1 selection.
The alarm is related to AL1.
Word modbus 2018
0 Disabled. > Default.
1 Absolute alarm, referring to measurement
(process)
2 Alarm band
 6QQFSEFWJBUJPOBMBSN
4 Lower deviation alarm
5 Absolute alarm, referring to setpoint
6 Alarm status (active in Run / Start)
7 Cooling output
8 Heater Break Alarm
9 Loop Break Alarm
10 Copy of OUT1
19
DVR
Alarm 1 State Output
Alarm 1 output contact and type of action
Word modbus 2019
0
Normally open, active from start. >
Default
.
1 Normally closed, active from start
2 Normally open, active from alarm reaching
1
 /PSNBMMZDMPTFEBDUJWFGSPNBMBSNSFBDIJOH
2
20
D+\
Alarm 1 Hysteresis
Word modbus 2020
LabSoftView:
-99.9..+99.9 degrees >
Default: 0
E.g. : 1 = 1 °C / °F
Modbus:
-999..+999 tenths of
degrees
E.g. : 10 = 1.0 °C / °F
2
At starting, the output is inhibited if the device is in alarm condition. It is
activated at each alarm start.
Vedere la pagina 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 102 103

Commenti su questo manuale

Nessun commento